Burner controller connection checking and test
Do you know how Ekgas burner controller connection checking and test?
Firstly check and ensure the live wire L, zero line N and other wires are well connected as specified;
Switch off the manual valve and start the system;
Close the switch on the burner controller 244 panel, with green light on; close the
switch, namely supply power to terminal 3 and start the operation procedure; in about 3 seconds, the gas solenoid valve is turned on, burner ignites; after the safe time, the burner controller gives out failure signal, and the red light on the panel is on, terminal 7 and 8 close; open the manual ball valve of the gas, then close the panel switch again, the controller will reset and release the failure signal; re-start the operation procedure: the burner ignites and yellow light on the panel is on, terminal 10 and 11 close, indicating good connection and normal system working.