Burner controller attentions
Do you know burner controller attentions? —Ekgas
The power cord shall be fixed, and live wire L and zero line N shall
Not be connected error in order to prevent equipment damage.
The solenoid valve and ignition transformer shall be driven by 220AC power source,
With max. output current 2A and each output current no greater than 2.5A.
Combustion indicator contact (terminals 13- 14) and ignition failure signal contact (terminals 8-9): max. current 2A, max. voltage: 253V.
Max. working voltage of UV flame detector: 230V, without internal fuse.
When a single electrode is used, the 7# terminal of the burner and controller must be earthed in order to prevent equipment damage.
In case of UV detector, the 7# terminal may not be earthed.
Terminals 11 and 12 have been parallel connected inside it.
Installation: 35 mm U-shaped rail can be used, width113mm, height 75mm and depth 120mm,
distance of two installation holes on the base plate.
An independent detection cable is used and in the protection of plastic cable pipe,
shall be separated from the main cable in case of remote control, to prevent electromagnetic interference.
Before power supply, the two fixation screws on the automatic burner controller must be screwed down.
The secondary ignition operation shall be done in 20 seconds after the alarm red light is on, to prevent overload damage.