Burner controller installation
Burner controller installation details Ekgas has the details –IFT244
Installation requirements
Ambient temperature: -20℃ – 65℃, without condensation.
An independent detection cable is used and in the protection of plastic cable pipe, shall be separated from the main cable,to prevent electromagnetic interference.
The live wire and zero line shall not be connected error, and the electric cabinet earth wire must be connected to the earth wire of the burner and the controller 244.
Power supply: AC220V, voltage fluctuation scope -15 / +10%, frequency 50HZ, no floating voltage being with the zero line (other power supply models can be customized).
Power: 18 VA+25 VA (ignition power 25VA).
Built-in ignition transformer, with ignition electrode clearance being 2-3mm and ignition high-voltage line <1 m.
The high-voltage line shall not pass through metal pipe and shall separate from the detection line.
Installation sizes: 35 mm U-shaped rail can be used, width113mm, height 75mm and depth 120mm.
Distance between two installation holes on the base plate is 70mm.
Fuse: 3.15A delay type H.