How to keep an industrial gas proportional valve works well?
Here let me explain as bellow:
Here let me explain as bellow:
Even good maintenance can’t compensate for a wrong valve.
Gas type: Natural gas, LPG, biogas, hydrogen blends → materials and seals must match
Flow range & control ratio: Ensure the valve operates mostly in 20–80% opening, not always near minimum
Pressure rating: Inlet pressure within the valve’s design range
Control signal: 0–10 V, 4–20 mA, PWM, or bus (Modbus/Profibus)
Safety standards: EN 161 / EN 88 / UL / CSA as required
✔ Oversized valves cause poor low-fire stability and hunting.
Bad installation is a common cause of failure.
Install a gas filter (≤50 μm) upstream
Maintain straight pipe length (≥5D upstream, ≥3D downstream)
Follow flow direction arrow
Ensure no pipe stress on valve body
Correct voltage and polarity
Shielded cables for analog signals
Good grounding to prevent signal noise
Separate power cables from ignition/high-voltage lines
Gas contamination damages proportional valves quickly.
Regularly clean or replace gas filters
Prevent:
Dust and rust particles
Oil or compressor condensate
Moisture (especially in biogas systems)
📌 Dirty gas = stuck plunger + unstable flame.
Unstable signals cause valve wear and poor combustion.
Verify controller output is:
Smooth (no oscillation)
Correct range (e.g., 4–20 mA never drops below 4 mA)
Use signal damping or PID tuning if the valve “hunts”
Avoid frequent full open–close cycling
Listen for abnormal noise or vibration
Check valve response at low fire and high fire
Inspect wiring terminals for looseness
Power off and isolate gas
Remove valve and:
Clean internal parts with dry air (no oil)
Inspect seals and diaphragm
Re-calibrate zero and span if adjustable
⚠ Never use aggressive solvents unless approved by the manufacturer.
Ambient temperature within spec (often –10 to +60 °C)
Protect from:
Water, steam, and condensation
Excessive vibration
Corrosive gases
For harsh environments, use IP65 / IP67 rated actuators.
Always pair with:
Gas solenoid safety shut-off valves
Pressure regulator upstream
Flame supervision system
Perform annual combustion tuning (O₂, CO, NOx)
A well-tuned burner greatly reduces proportional valve stress.
| Problem | Likely Cause |
|---|---|
| Valve stuck | Dirty gas / no filter |
| Flame instability | Oversized valve / bad PID |
| Slow response | Low voltage / worn actuator |
| Overheating | Continuous max load |
| Signal drift | Poor grounding |
✅ Clean gas
✅ Correct sizing
✅ Stable control signal
✅ Good grounding
✅ Periodic calibration