How to turn on an industrial gas burner?
How to turn on an industrial gas burner
1. Pre-start safety checks (don’t skip this)
Before touching the start button:
-
✔️ Gas supply is available and pressure is within design range
-
✔️ Main gas shut-off valve is closed
-
✔️ Air blower / fan is ready to run
-
✔️ Combustion chamber is clear (no unburned gas inside)
-
✔️ No gas leaks (smell test + detector if available)
-
✔️ All safety devices are OK:
-
Air pressure switch
-
Flame detector (UV / ionization / IR)
-
Emergency stop reset
⚠️ If anything fails here, do not start.
2. Start the combustion air system
-
Start the combustion air fan/blower
-
Verify:
-
Air pressure switch closes
-
Airflow is stable
-
-
Set air damper to purge/start position
👉 Air must always start before gas
3. Purge the combustion chamber
-
The control system will run a pre-purge (typically 30–60 seconds)
-
Fresh air removes any residual gas
📌 Purge time is critical—never shorten it manually.
4. Enable ignition system
Once purge is complete:
-
Ignition transformer / spark igniter turns ON
-
Pilot gas solenoid (if equipped) opens
-
Some burners use direct spark ignition (no pilot)
-
5. Light the pilot flame (if applicable)
-
Pilot gas ignites
-
Flame detector must confirm flame within 2–5 seconds
❌ If flame is NOT detected:
-
System will lock out
-
You must investigate and reset before retrying
6. Open main gas valve
After pilot confirmation:
-
Main gas solenoid valve opens
-
Main burner ignites from pilot (or direct spark)
-
Flame detector confirms main flame
7. Burner enters normal operation
-
Burner control switches to run mode
-
Air–gas ratio control takes over
-
Modulating burner adjusts output based on temperature demand
🔥 Burner is now ON and stable
8. Monitor during first minutes
Watch closely for:
-
Stable flame (no lifting or flashback)
-
Smooth sound (no banging or pulsation)
-
Correct gas & air pressure
-
No alarms or flame failure trips
Common startup mistakes (very important)
❌ Opening gas before air
❌ Skipping purge
❌ Repeated reset without fixing flame failure
❌ Starting with incorrect gas pressure
❌ Dirty flame sensor or blocked burner head
Quick startup flow (easy to remember)
Air → Purge → Ignite → Pilot → Main Gas → Run
Phone: 86 185 6630 3837
WhatsApp: 86 185 66303837
Email: ekeilairn@gmail.com
www.http://ekgas.com
Categories
Popular tags
Latest Posts
July 28, 2025
Do you know electric actuator?
February 12, 2026
How to use an industrial gas proportional valve
February 11, 2026
How to use an industrial gas solenoid valve
February 10, 2026
How to use an industrial gas filter
February 9, 2026
How to turn on an industrial gas burner
February 7, 2026
Leave a comment