How to know gas solenoid valve works well?
To know whether a gas solenoid valve is working well, you can check it from electrical, mechanical, and functional aspects. Ekgas here’s a clear and practical checklist:
How to Know if a Gas Solenoid Valve Works Well
1. Listen for the “Click” Sound
When power is supplied to the solenoid coil, a healthy valve usually produces a distinct click as the internal plunger moves.
-
✔ Clear “click” = valve is opening/closing
-
✘ No sound = coil may be burnt, plunger stuck, or no power supplied
2. Check Opening & Closing Function
Make sure the valve responds correctly to control signals.
Test Method
-
Power ON: valve should open
-
Power OFF: valve should close
-
Observe whether gas flow starts/stops accordingly.
-
✔ Fast response
-
✔ Stable operation
-
✘ Slow or no response = mechanical or electrical issue
3. Measure Coil Voltage
Use a multimeter to measure the coil voltage.
-
Compare actual voltage with nameplate rating (e.g., 12VDC, 24VDC, 220VAC)
-
✔ Voltage within ±10% = normal
-
✘ Too low = may fail to open
-
✘ Too high = may burn coil
4. Check Coil Temperature
A solenoid coil becomes warm in normal use, but it should not be too hot to touch.
-
✔ Warm = normal
-
✘ Very hot = coil overload, incorrect voltage, or internal short
5. Check for Gas Leakage
Use soap solution or a leak detector around fittings and valve body.
-
✔ No bubbles = no leak
-
✘ Bubbles = sealing failure or installation issue
6. Inspect Filter & Valve Internals
Dust or debris can block the plunger.
-
Remove inlet filter and clean it
-
If the plunger is dirty or sticky → clean or replace it
7. Check Pressure Ratings
Ensure gas pressure fits the valve’s specification.
-
✔ Inlet pressure within design range
-
✘ Too high = valve may not close properly
-
✘ Too low = may not open fully
8. Check Current Consumption
Measure coil current with multimeter clamp.
-
✔ Current matches datasheet
-
✘ Too high = coil damage
-
✘ Too low = internal coil break
Common Signs a Gas Solenoid Valve Is Not Working
-
No “click” sound
-
Gas flow does not stop when valve closes
-
Valve becomes extremely hot
-
Slow opening or closing
-
Leakage around connections
-
Coil smells like burning
-
Voltage correct but valve still not operating